DAMPER ACTUATORS JOVENTA

JOVENTA ACTUATORS
DAMPER ACTUATORS JOVENTA WITH SPRING RETURN

Springback 3 Nm
The electric springback actuators of the JOVENTA® SPRINGBACK series have been specially developed for motorizing safety dampers (frost protection) in air-conditioning systems as well as for smoke dampers and sealing dampers with safety function. When the control voltage is applied, the actuator moves the damper to the operating position while simultaneously tensioning the integrated spring. When the voltage is switched off or fails, the actuator returns to the initial position (safety position) with the aid of the spring.
Universal adapter for: Rotary axes 6…12 mm Ø and square axes
6…8 mm SW as well as minimum axis length 20 mm (clamping block under the drive, otherwise 84 mm).
DAF1.03
Torque 3 Nm, dampers up to 0.6 m²
Running time motor 60 s, spring 12…17 s
Supply voltage 24 V AC
Control 2-point, cable connection
no auxiliary switches
DAF1.03S
Torque 3 Nm, dampers up to 0.6 m²
Running time motor 60 s, spring 12…17 s
DBF1.03
Torque 3 Nm, dampers up to 0.6 m²
Running time motor 150 s, spring 12…17 s
Supply voltage 24 V AC
Control 2-/3-point, cable connection
no auxiliary switches
DBF1.03S
Torque 3 Nm, dampers up to 0.6 m²
Running time motor 150 s, spring 12…17 s
Supply voltage 24 V AC
Control 2-/3-point, cable connection
1 auxiliary switch
DBF1.03Z
Torque 3 Nm, dampers up to 0.6 m²
Running time motor 90 s, spring 12…17 s
Supply voltage 24 V AC
Control 2-/3-point, high-speed, cable connection
no auxiliary switches
DBF1.03SZ
Torque 3 Nm, dampers up to 0.6 m²
Running time motor 90 s, spring 12…17 s
Supply voltage 24 V AC
Control 2-/3-point, high-speed, cable connection
1 auxiliary switch
DMF1.03
Torque 3 Nm, dampers up to 0.6 m²
Running time motor 150 s, spring 12…17 s
Supply voltage 24 V AC
Control 0(2)…10 V DC, cable connection
no auxiliary switches
DMF1.03S
Torque 3 Nm, dampers up to 0.6 m²
Running time motor 150 s, spring 12…17 s
Supply voltage 24 V AC
Control 0(2)…10 V DC, cable connection
1 auxiliary switch
DMF1.03Z
Torque 3 Nm, dampers up to 0.6 m²
Running time motor 90 s, spring 12…17 s
Supply voltage 24 V AC
Control 0(2)…10 V DC, high-speed, cable connection
no auxiliary switches
DMF1.03SZ
Torque 3 Nm, dampers up to 0.6 m²
Running time motor 90 s, spring 12…17 s
Supply voltage 24 V AC
Control 0(2)…10 V DC, high-speed, cable connection
1 auxiliary switch
DAF2.03
Torque 3 Nm, dampers up to 0.6 m²
Running time motor 60 s, spring 12…17 s
Supply voltage 230 V AC
Control 2-point, cable connection
no auxiliary switches
DAF2.03S
Torque 3 Nm, dampers up to 0.6 m²
Running time motor 60 s, spring 12…17 s
Supply voltage 230 V AC
Control 2-point, cable connection
1 auxiliary switch
DAF2.03Z
Torque 3 Nm, dampers up to 0.6 m²
Running time motor 27 s, spring 12…17 s
Supply voltage 230 V AC
Control 2-point, high-speed, cable connection
no auxiliary switches
DAF2.03SZ
Torque 3 Nm, dampers up to 0.6 m²
Running time motor 27 s, spring 12…17 s
Supply voltage 230 V AC
Control 2-point, high-speed, cable connection
1 auxiliary switch

Springback 8 Nm
The electric springback actuators of the JOVENTA® SPRINGBACK series have been specially developed for motorizing safety dampers (frost protection) in air-conditioning systems as well as for smoke dampers and sealing dampers with safety function. When the control voltage is applied, the actuator moves the damper to the operating position while simultaneously tensioning the integrated spring. When the voltage is switched off or fails, the actuator returns to the initial position (safety position) with the aid of the spring.
Universal adapter for: Rotary axes 8…16 mm Ø and square axes
6…12 mm SW as well as minimum axis length 20 mm (clamping block under the drive, otherwise
84 mm).

Springback 16 Nm
The electric springback actuators of the JOVENTA® SPRINGBACK series have been specially developed for motorizing safety dampers (frost protection) in air-conditioning systems as well as for smoke dampers and sealing dampers with safety function. When the control voltage is applied, the actuator moves the damper to the operating position while simultaneously tensioning the integrated spring. When the voltage is switched off or fails, the actuator returns to the initial position (safety position) with the aid of the spring.
Universal adapter for: Rotary axes 10…20 mm Ø and square axes
10…16 mm SW and minimum axis length 72 mm.

Springback 20 Nm
The electric springback actuators of the JOVENTA® SPRINGBACK series have been specially developed for motorizing safety dampers (frost protection) in air-conditioning systems as well as for smoke dampers and sealing dampers with safety function. When the control voltage is applied, the actuator moves the damper to the operating position while simultaneously tensioning the integrated spring. When the voltage is switched off or fails, the actuator returns to the initial position (safety position) with the aid of the spring.
Universal adapter for: Rotary axes 12…19 mm Ø and square axes
10…14 mm SW as well as minimum axis length 80 mm (45 mm with clamping block under the drive).
DBF1.20S
Torque 20 Nm, dampers up to 5 m²
Running time motor 24…57 s, spring 11…15 s
Supply voltage 24 V AC/DC
Control 3-point, cable connection
2 auxiliary switches

Security Fire 8 Nm
The electric spring return actuators of the JOVENTA® SECURITY FIRE series have been specially developed for the motorization of fire dampers. After applying the supply voltage, the actuator moves the damper to the operating position (OPEN) while simultaneously tensioning the integrated spring. If the power supply to the actuator is interrupted, the stored spring energy immediately moves the damper to the fail-safe position (CLOSED). The manual position fixing by means of a hand crank is automatically cancelled when the actuator is operated electrically. Depending on the version, the actuators are equipped with thermal sensors for duct and/or environment which trigger the spring return when a temperature of 72 °C is exceeded. The simplest version does not have thermal sensors.
Installation on damper axis: integrated 12 mm square axis adapter as well as optional adapters for 10 mm and 8 mm square axes.
SAF1.08Sx/12
Torque 8 Nm,
Running time motor 60 s nominal, spring 21 s nominal
Supply voltage 24 V AC/DC
Control 2-point, cable connection
two fixed auxiliary switches (at 8° and 83° opening angle)
Datasheet
SAF1.08Sx/12
Torque 8 Nm,
Running time motor 60 s nominal, spring 21 s nominal
Supply voltage 230 V AC
Control 2-point, cable connection
two fixed auxiliary switches (at 8° and 83° opening angle)
Datasheet

Security Fire 10 and 16 Nm
The electric spring return actuators of the JOVENTA® SECURITY FIRE series have been specially developed for the motorization of fire dampers. After applying the supply voltage, the actuator moves the damper to the operating position (OPEN) while simultaneously tensioning the integrated spring. If the power supply to the actuator is interrupted, the stored spring energy immediately moves the damper to the fail-safe position (CLOSED). Manual position fixing by means of a hand crank is automatically cancelled when the actuator is operated electrically. Integrated thermosensor for ambient temperature, connection possibility for duct thermosensor.
Installation on damper shaft: depending on version, integrated steel adapter for square shafts with edge length 10, 11, 12 or 14 mm.

Security Fire 10 and 16 Nm - SLC system
The electric spring return actuators of the JOVENTA® SECURITY FIRE series have been specially developed for the motorization of fire dampers. After applying the supply voltage, the actuator moves the damper to the operating position (OPEN) while simultaneously tensioning the integrated spring. If the power supply to the actuator is interrupted, the stored spring energy immediately moves the damper to the fail-safe position (CLOSED). Manual position fixing by means of a hand crank is automatically cancelled when the actuator is operated electrically.
Integrated thermosensor for ambient temperature, connection possibility for duct thermosensor. Control, monitoring and power supply via 2-wire cable from module JSLC-B.
Installation on damper axis: depending on version, integrated steel adapter for square axes with edge length of 10, 11, 12 or 14 mm.

Security Fire - Smoke Extraction Damper Actuators
The electric actuators of the JOVENTA SECURITY SMOKE seriesSE… have been specially developed for the motorization of smoke extraction dampers. The actuator motorizes the damper to the safety position (damper open). In the event of a voltage interruption, the gear is mechanically and reliably locked. The actuator thus meets the requirements of DIN V 18232 T6. As long as the supply voltage is not interrupted, the damper can be closed again with the actuator by authorized rescue personnel (fire department) using a motor, in order to specifically seal off sections of the building from the passage of smoke.
Installation on damper axis: depending on version, integrated steel adapter for square axes with edge length 10, 11, 12 or 14 mm

Security Fire - Smoke extraction damper actuators, SLC system
The electric actuators of the JOVENTA SECURITY SMOKE series SE… have been specially developed for the motorization of smoke extraction dampers. The actuator motorizes the damper to the safety position (damper open). In the event of a voltage interruption, the gear is mechanically and reliably locked. The actuator thus meets the requirements of DIN V 18232 T6. As long as the supply voltage is not interrupted, the damper can be closed again by authorized rescue personnel (fire department) using the motor, in order to specifically seal off sections of the building from the passage of smoke. Control, monitoring and power supply are provided via a 2-wire cable from the JSLC-R module.
Installation on damper axis: depending on version, integrated steel adapter for square axes with edge length 10, 11, 12 or 14 mm
SE.1.90.SLC
Supply voltage and 2-point control from SLC control module via 2-wire line, terminal connection, end position monitoring via SLC control module

Security Fire - Smoke, safety actuator for smoke extraction dampers with venting function, SLC system.
The electric actuators of the JOVENTA SECURITY SMOKE seriesSE…SLC AKO have been specially developed for motorizing smoke extraction dampers with a venting function. In normal operation (no fire alarm), these dampers serve as normal exhaust dampers. In the event of an alarm, the dampers are closed by motor to prevent the spread of smoke. As long as the supply voltage is not interrupted, the damper with the actuator can be opened again by motor by authorized rescue personnel (fire department) in order to remove smoke from specific sections of the building. If the power supply is interrupted, the actuator still executes the last command received with the help of the integrated rechargeable battery and then locks the gear mechanically. The actuator thus meets the requirements of DIN V 18232 T6. Control, monitoring and power supply are provided via a 2-wire line from the JSLC-K module.
Installation on damper axis: integrated steel adapter for square axes with edge length 12 mm
.SE. 1.90SLC/12 AKO
Torque 52 Nm, angle of rotation 360 ° (end stops must be realized in flap), running time up to
65 s for 90°
Supply voltage and 2-point control from SLC control module via 2-wire line, terminal connection, end position monitoring via SLC control module
Datasheet