Ueber uns
Hubventile Kleinventile

Small valves series KVDN

The small valves of the KVDN series are available as globe and three-way valves as well as three-way valves with bypass in the nominal diameters DN 10, DN 15 and DN 20. With their temperature range of +2 … +120 °C, they are predestined for heating applications. The nominal pressure PN 16 identifies them as high-quality components. The valve bodies have external threads for connection to the pipeline. Threaded, soldered and compression fittings are available as accessories. For actuation, the range includes modulating and OPEN/CLOSED actuators in electrothermal and electromechanical versions.

Datasheet

Globe valve

KVDN10/2/0.16

Nominal size - male thread

DN10 – G1/2B

Kvs in m3/h

0,16

KVDN10/2/0.4

Nominal size - male thread

DN10 – G1/2B

Kvs in m3/h

0,4

KVDN10/2/0.63

Nominal size - male thread

DN10 – G1/2B

Kvs in m3/h

0,63

KVDN10/2/1.0

Nominal size - male thread

DN10 – G1/2B

Kvs in m3/h

1,0

KVDN10/2/1.6

Nominal size - male thread

DN10 – G1/2B

Kvs in m3/h

1,6

KVDN15/2/2.5

Nominal size - male thread

DN15 – G3/4B

Kvs in m3/h

2,5

KVDN15/2/3.5

Nominal size - male thread

DN15 – G3/4B

Kvs in m3/h

4,0 (3,5*)* Globe valve

KVDN20/2/4.5

Nominal size - male thread

DN20 – GB

Kvs in m3/h

5,0 (4,5*) * Globe valve

Three-way valve

KVDN10/3/0.4

Nominal size - male thread​

DN10 – G1/2B

Kvs in m3/h

0,4

KVDN10/3/0.63

Nominal size - male thread​

DN10 – G1/2B

Kvs in m3/h

0,63

KVDN10/3/1.0

Nominal size - male thread​

DN10 – G1/2B

Kvs in m3/h

1,0

KVDN10/3/1.6

Nominal size - male thread​

DN10 – G1/2B

Kvs in m3/h

1,6

KVDN15/3/2.5

Nominal size - male thread​

DN15 – G3/4B

Kvs in m3/h

2,5

KVDN15/3/4.0

Nominal size - male thread​

DN15 – G3/4B

Kvs in m3/h

4,0 (3,5*)* Globe valve

KVDN20/3/5.0

Nominal size - male thread​

DN20 – GB

Kvs in m3/h

5,0 (4,5*) * Globe valve

Three-way with bypass

KVDN10/3B/0.4

Nominal size - male thread

DN10 – G1/2B

Kvs in m3/h

1,0

KKVDN10/3B/0.63

Nominal size - male thread

DN10 – G1/2B

Kvs in m3/h

0,4

KVDN10/3B/1.0

Nominal size - male thread

DN10 – G1/2B

Kvs in m3/h

0,63

KVDN10/3B/1.6

Nominal size - male thread

DN10 – G1/2B

Kvs in m3/h

1,6

KVDN15/3B/2.5

Nominal size - male thread

DN15 – G3/4B

Kvs in m3/h

2,5

KVDN15/3B/4.0

Nominal size - male thread

DN15 – G3/4B

Kvs in m3/h

4,0 (3,5*)* Globe valve

KVDN20/3B/5.0

Nominal size - male thread

DN20 – GB

Kvs in m3/h

5,0 (4,5*) * Globe valve

Electrothermal drives

VA115.1

24V AC, 2-point,
running time 3,5 min,
stroke 4.5 mm,
actuating force 115 N

VA115.2

230V AC, 2-point
Running time 3.5 min,
stroke 4.5 mm,
actuating force 115 N

VA115.1M

24 V AC, 0…10 V DC
Running time 4.5 min,
stroke 4.5 mm,
actuating force 115 N

Electromechanical drives

VA120.1

24 V AC/DC, 3-point,
running time 50 s,
stroke max. 6.3 mm
Actuating force 120 N

VA120.2

230 V AC, 3-point,
running time 50 s,
stroke max. 6.3 mm,
positioning force 120 N

VA120.1M

24 V AC/DC, 0…10 V DC, running time 50 s,
stroke max. 6.3 mm,
positioning force 120 N